Included:
Outdoor Sensor 070, Universal Sensor 082
|
|
Dimensions:
5" H x 3-1/4" W x 15/16" D (127 x 82 x 23 mm)
|
|
Ambient conditions:
-4 to 122°F (-20 to 50°C), <90% RH non-condensing, outdoor use permitted when installed inside a NEMA 3 enclosure
|
|
Enclosure:
White PVC plastic, NEMA type 1
|
|
Control:
Microprocessor control. This is not a safety (limit) control
|
|
Warranty:
Limited 3 Year Warranty
|
|
Sensors:
NTC thermistor, 10 k? @77°F (25°C ±0.2°C) ß=3892
|
|
Power supply:
24 V (ac) ±10%, 60 Hz, Class 2, 16 VA standby, 100 VA fully loaded
|
|
Relay capacity:
24 V (ac) 2 A, 3.6 A combined
|
|
Modulating output:
0-10 V (dc), 500 ? minimum load impedance, 4-20 mA 1 k? max load impedance
|
|
Optional:
tekmar type #: 072, 073, 090, 091, 094, 095
|