The Zone Valve Control 306V connects up to six thermostats and operates zone valves to provide heating to a zoned hydronic heating system. The 306V operates a system pump whenever a zone valve opens. Zone 1 can operate either a zone valve or a circulator to provide heat to an indirect domestic hot water tank with optional priority over zones 2 through 6. The 306V includes optional exercising to prevent circulator seizure when not in use, and optional post purge operation of the domestic hot water tank to maximize energy savings. The 306V provides a RoomResponse™ signal to modulating-condensing boilers to optimize comfort while improving boiler efficiency.

  • RoomResponse™ signal, compatible with all low voltage thermostats
  • Compatible with 2, 3 and 4-wire zone valves, unlimited zone expansion
  • Zone priority, priority override
  • Pump exercising, post purge
  • LED for each zone, priority, end switch and RoomResponse™, away signal shared between tekmar thermostats
  • Four ground screws, Top, bottom and back conduit knockouts
  • Fuses protect transformers and pumps
  • Two spare fuses included
  • CSA approved
232.31 232.31

  • Dimensions
  • Ambient conditions
  • Approvals
  • Enclosure
  • Control
  • Warranty
  • Packaged weight
  • Mod boiler output
  • DHW end switch
  • Boiler XX end switch
  • Power supply
  • Transformer
  • Fuses
  • Zone valve end switch
  • Zone valve outputs
  • Control load
  • System Pump
Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days
Dimensions: 8-3/16" H x 10-11/16" W x 2-3/8" D (208 x 271 x 60 mm)
Ambient conditions: Indoor use only, 32 to 122°F (0 to 50°C), RH ?90% non-condensing
Approvals: CSA C US
Enclosure: Cover: ABS plastic, Base: galvanized steel, NEMA type 2
Control: Microprocessor control. This is not a safety (limit) control.
Warranty: Limited 3 Year Warranty
Packaged weight: 5.0 lb. (2250 g)
Mod boiler output: 0-10 V (dc) 500 ? min load impedance / 4-20 mA 1 k? max load impedance
DHW end switch: 24 V (ac), 5 A
Boiler XX end switch: 24 V (ac), 5 A
Power supply: 115 V (ac) ±10%, 60 Hz, 20 A
Transformer: 80VA
Fuses: T5A 250 V slow blow, two spare fuses included
Zone valve end switch: 24 V (ac)
Zone valve outputs: 24 V (ac), 2 A max per output
Control load: 7 VA
System Pump: 230 V (ac), 5 A, 1/3 hp