Skip to Content

360

Mixing Control 360

The Mixing Control 360 is designed to operate a mixing valve using Outdoor Temperature Reset. It can be used in applications ranging from in-floor radiant to commercial baseboard systems for Boiler Return Protection with full reset. This control regulates a single heating water temperature through Mixing Outdoor Reset. It controls the mixing by opening or closing a floating action type mixing valve actuator (3 or 4 way valves), and also provides control of the mix system pump.


Features

  • CSA C US certified (approved to applicable UL standards)

  • Test sequence to ensure proper component operation

  • Floating action mixing control, powered mixing system pump output

  • Setback input for energy savings

  • Quick setup for easy installation and programming of control

  • Outdoor temperature reset, indoor temperature feedback (with optional indoor sensor)

  • Warm weather shut down, automatic boiler differential

  • User comfort adjustment to increase or decrease building space temperature

  • Advanced settings to fine-tune building requirements

700.16 700.16

  • Dimensions
  • Ambient conditions
  • Approvals
  • Enclosure
  • Control
  • Relays
  • Warranty
  • Sensors
  • Packaged weight
  • Power supply
  • Floating output
  • Demand
  • –Included
  • –Optional
Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days
Dimensions: 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm)
Ambient conditions: Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Noncondensing
Approvals: CSA C US, meets class B: ICES & FCC Part 15
Enclosure: Blue PVC plastic, NEMA type 1
Control: Microprocessor control. This is not a safety (limit) control
Relays: 240 V (ac) 10 A 1/3 hp
Warranty: Limited 3 Year (See D360 for full warranty)
Sensors: NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
Packaged weight: 3.1 lb. (1420 g)
Power supply: 120 V (ac) ±10%, 50/60 Hz, 1300 VA
Floating output: 24 V (ac) 0.34 A 8 VA
Demand: 20 to 260 V (ac) 2 VA
–Included: Outdoor Sensor 070 and 2 of Universal Sensor 082
–Optional: tekmar type #: 033, 076, 077, 084